1
Schneider 40A tetra circuit breaker
60,00 €
Inklusive Steuer
R9F64440
0712971133402
• Schneider 40A Circuit Breaker
• RESI9
• 4 poles
In view of the current situation concerning the reordering of products and the uncertain deadlines communicated by our suppliers, we cannot guarantee to supply you with a Schneider brand circuit breaker.
However, as an alternative, we can provide you with a Hager circuit breaker with the same characteristics.
Main | |
range | Resi9 |
Product name | Resi9 MCB |
Product or component type | Miniature circuit breaker |
Application of the device | distribution |
Description of the poles | 4P |
Number of poles protected | 4 |
[In] assigned current job | 40 A to 30 degrees Celsius |
Type of network | Ac. |
Trigger technology | Thermal-magnetic |
Trigger curve | c |
Cutting power | 3000 A Icn at 400 V c.a. 50/60 Hz compliant with EN/IEC 60898-1 |
Standards | EN/IEC 60898-1 |
Product certifications | CEBEC |
Complementary | |
Frequency of network | 50/60 Hz |
[Ue] assigned job tension | 400 V AC 50/60 Hz |
Magnetic trigger limit | 5...10 x In |
Limitation class | 3 according to EN/IEC 60898-1 |
[Ui] assigned isolated tension | 440 V AC 50/60 Hz |
[Uimp] assigned tension of holding to shocks | 4 kV |
Type of command | Rocking key |
Local signage | IndicationACTIVE/DEACTIVE |
How to install | In clips |
Mounting support | Rail DIN |
Distribution block and comb compatibility | Bottom: bi-connect |
No 9 mm | 8 |
height | 85 mm |
width | 72 mm |
depth | 75 mm |
Depth of recess | 44 mm |
Product weight | 0.43 kg |
colour | White |
Mechanical lifespan | 20,000 cycle |
Electric lifespan | 10000 cycle c.a. 50/60 Hz compliant with EN/IEC 60898-1 |
Description of optional locks | Cadenas on OFF position |
Connection mode | Tunnel-type terminals (bottom) - < 16 mm2 - flexible Tunnel-type terminals (bottom) - < 25 mm2 - rigid Tunnel-type terminals (top) - < 25 mm2 - rigid Tunnel-type terminals (top) - < 16 mm2 - flexible |
Tightening torque | 2 N.m |
environment | |
Degree of IP protection | IP20 compliant with IEC 60529 IP40 (modular box) compliant with IEC 60529 |
Pollution level | 2 EN/IEC 60898-1 |
Surge category | Iii |
Operating temperature | -20 to 60 degrees Celsius |
Room temperature for storage | -40 to 80 degrees Celsius |