Differential switch type A 2P 63A 30ma

€ 100,50
Inclusief belasting
SERR9R01263
0712971133617

Differential switch type A 2P 63A 30ma

Differential switch type A...

€ 100,50

Differential switch type A 2P 63A 30ma

Function

Differential switches are devices that are placed in front of them and protect against leakage currents to earth unacceptable. They protect people against electric shock.

 

Operation

In case of a leakage current with a residual pulsating direct current, an imbalance appears in the primary coil of the toroid, thereby generating a residual magnetic field in the core. This residual magnetic field in turn generates a voltage and a current in the secondary coil which solicits over. The relay in turn solicits the release device and open the contacts under spring pressure.


Main features
RangeResi9
Product nameResi9 RCCB
Product functionResidual current circuit breaker (RCCB)
NShort name of the deviceResi9 RCCB
Description of the poles2P
Position of the neutral poleLeft
Rated operational current63 A
Network typeCA
Differential sensitivity30 mA
Differential TimingInstant
Differential ClassClasse A
Rated breaking and closing capacityIm 500 A
Conditional short-circuit current6 kA 40 A
Additionnal features
Network frequency50/60 Hz
[Ue] rated operating voltage230 V CA 50/60 Hz
Type of controlRocker key
Local indicationIndication ON/OFF
Installation modeSnap-in
Mounting bracketDIN rail
Compatibility of the busbar comb distribution blockBiconnect
Step of 9 mm4
Height100 mm
Width40 mm
Depth82 mm
Weight0.194 kg
ColourWhite
Mechanical life5000 cycles
Electrical lifeAC-1 :
Connection typeTerminals tunnel type flexible wire (s) 1 ... 25 mm² max without cable end
Terminals tunnel type flexible wire (s) 1 ... 25 mm² max with cable end
Tunnel type terminals rigid wire (s) 1 ... 35 mm² max
Tightening torque3.5 N.m
Environment
StandardsEN 61008-2-1
IEC 61008-2-1
Quality labelsCEBEC
Degree of protectionIP20
Operating Temperature-25…40 °C
Ambient temperature for storage-30…70 °C
Sustainability of the offer
Environmental product statusGreen Premium product
RoHS (code date: YearWeek)Compliant - since 1329 - Declaration of Conformity Schneider Electric
REAChReference not containing SVHC above threshol
Environmental Product ProfileAvailable
Product end-of-life instructionsNo specific recycling operation

 

 

SERR9R01263

Datasheet

Type elektrische apparatuur
Interrupteur

Specifieke referenties

upc
712971133617
ean13
0712971133617
Nieuw