Samsung FJM R32 outdoor unit from 4kW to 10kW
Samsung outdoor units:
AJ040TXJ2KG/EU
AJ050TXJ2KG/EU
AJ052TXJ3KG/EU
AJ068TXJ3KG/EU
AJ080TXJ4KG/EU
AJ100TXJ5KG/EU
One outdoor unit, several indoor units
When you want to heat or cool multiple spaces, Samsung's Free Joint Multi system offers you the perfect solution. With a single outdoor unit and up to 5 interior units, this ultra-silent system easily creates a perfect indoor climate. You also have a lot of freedom to choose models and abilities.
Its modulating capacity regulation makes the Free Joint Multi an extremely economical system.
Flexibility
Samsung's compact Free Joint Multi system offers you the perfect solution when you want to heat or cool multiple rooms, such as your living room and bedroom, or a closet, waiting room or office.
Depending on the occupancy in the different rooms, you can turn on the number of interior units you want. The modulating capacity regulation allocates proportionally the available capacity between the activated units.
The big advantage is that you only heat or cool the parts you use. An energy-efficient solution!
Your benefits in a nutshell
Heating, cooling and dehumiding with a single system
Up to a maximum of 5 indoor units for an outdoor unit
Freedom of choice of the type of inner unit
Heating very low energy and fast
Capacity regulation, up to 170% simultaneous
Optimal comfort all year round
Samsung's Free Joint Multi system, equipped with a heat pump, can heat and cool the room very quickly, using little energy. Therefore, with a Samsung heat pump, you can enjoy a pleasant indoor temperature in all seasons, while making considerable savings on your energy bill!
Fast heating
The big advantage of heating with an air heat pump is that the desired temperature is quickly reached. Indeed, the hot air blown into the room ensures a quick and comfortable heating. When the system is turned off, the residual heat is virtually zero and the room cools relatively quickly.
This is the ideal system for a room for example, where locals want to study warm but sleep in a cool place. Get advice from your installer to find out what's the best solution for your situation.
Several models of interior units
With the Free Joint Multi system, you can choose from several interior units. Placed high on the wall, the wall models are ideal when there is no false ceiling. Thanks to their stylish design, the units offer an added valuer to each interior. If the wall installation is not desirable or possible, the recessed models can be used.
For example, cassette models are embedded in the ceiling, where only the aesthetic panels remain visible. The sheathable models are fully integrated into a (false) ceiling and offer optimal comfort. The console model is placed on the ground against the wall. Discover the possibilities of Samsung's Free Joint Multi system!
Air dehumidification
Besides a pleasant temperature, the humidity of the air is also a very important factor for our comfort.
Our body regulates its own temperature by releasing moisture. If the air around us is saturated and can no longer absorb this moisture, we have heat release problems and feel the sensation
unpleasant to stick and suffocate. A Samsung heat pump not only heats and cools, but also dehumidifies the air during cooling.
Samsung Wind-Free™: a cooling without draft
Wind-Free™ is the revolutionary new way to cool without air current. Thanks to the thousands of microperforations in the box, the air is blown at low speed.
Samsung Wind-Free™ is available in combination with a Free Joint Multi system for the wall model, the 1-way cassette and the 4-way mini-cassette.
Silent operation of the external unit
The interior units of the Free Joint Multi, equipped with a Twin BLDC compressor, are extremely quiet.
The FJM compressor is covered with two layers of acoustic insulation that absorbs and reduces noise.
Technical data
Model | AJ040TXJ2KG/EU | AJ050TXJ2KG/EU | AJ052TXJ3KG/EU | AJ068TXJ3KG/EU | AJ080TXJ4KG/EU | AJ100TXJ5KG/EU | ||
Ability | ||||||||
Ability | Cooling (nominal) | Kw | 4.0 | 5.0 | 5.2 | 6.8 | 8.0 | 10.0 |
Heating up -7 degrees Celsius | Kw | 4.2 | 5.6 | 6.3 | 8.0 | 9.3 | 12.0 | |
Heating up --5C | Kw | 3.16 | 4.22 | 4.22 | 6.02 | 7.00 | 9.03 | |
Heating - 10 degrees Celsius | Kw | 2.70 | 3.60 | 3.60 | 5.14 | 5.97 | 7.70 | |
Heating - 15 degrees Celsius | Kw | 2.23 | 2.98 | 2.98 | 4.25 | 4.94 | 6.38 | |
Performance | ||||||||
Energy efficiency of cooling | SEER | W/W | 8.54 | 8.54 | 8.51 | 7.75 | 7.75 | 8.00 |
Energy consumption | kWh/a | 164 | 205 | 206 | 293 | 330 | - | |
Declared refrigeration charge | Kw | 4.0 | 5.0 | 5.0 | 6.5 | 7.3 | - | |
Era | W/W | 4.44 | 4.10 | 4.16 | 3.78 | 4.06 | 3.64 | |
Energy efficiency of heating | Scop | W/W | 4.60 | 4.64 | 4.60 | 4.32 | 4.10 | 4.32 |
Energy consumption | kWh/a | 922 | 1,270 | 1,400 | 1,833 | 2,009 | - | |
Declared calorific charge (average) | Kw | 3.1 | 4.22 | 4.60 | 5.7 | 5.9 | - | |
Cop | W/W | 4.64 | 4.38 | 4.77 | 4.42 | 4.37 | 4.26 | |
Air flow | m3/min | 29.7 | 33.1 | 38.0 | 47.5 | 47.5 | 75.0 | |
Acoustic power | dB(A) | 60 | 61 | 61 | 64 | 64 | 70 | |
Acoussitque pressure | Cooling | dB(A) | 45 | 46 | 46 | 48 | 48 | 54 |
Heating | dB(A) | 46 | 47 | 48 | 50 | 50 | 56 | |
Fan | Type | Helical | Helical | Helical | Helical | Helical | Helical | |
Winding direction | Front (horizontal) | Front (horizontal) | Front (horizontal) | Front (horizontal) | Front (horizontal) | Front (horizontal) | ||
Power | W | 40 | 40 | 125 | 125 | 125 | 125 | |
Number of fans | - | 1 | 1 | 1 | 1 | 1 | 1 | |
Operating range | Cooling | ℃ | -5.0-46.0 | -5.0-46.0 | -10.0-46.0 | -10.0-46.0 | -10.0-46.0 | -10.0-46.0 |
Heating | ℃ | -15-24 | -15-24 | -15-24 | -15-24 | -15-24 | -15-24 | |
Installation data | ||||||||
Voltage | Φ, V, Hz | 1,220-240V, 50Hz | 1,220-240V, 50Hz | 1,220-240V, 50Hz | 1,220-240V, 50Hz | 1,220-240V, 50Hz | 1,220-240V, 50Hz | |
Type of compressor | Twin BLDC Rotary | Twin BLDC Rotary | Twin BLDC Rotary | Twin BLDC Rotary | Twin BLDC Rotary | Twin BLDC Rotary | ||
Energy consumption | Cooling | Kw | 0.90 | 1.22 | 1.25 | 1.80 | 1.97 | 2.75 |
Heating | Kw | 0.90 | 1.28 | 1.32 | 1.81 | 2.13 | 2.82 | |
Nominal current | Cooling | Has | 4.1 | 5.6 | 5.5 | 8.1 | 8.9 | 12.2 |
Heating | Has | 4.1 | 5.9 | 6.1 | 8.2 | 9.5 | 12.8 | |
Size | ||||||||
Size | (LxHxP) | Mr | 790x548x285 | 790x548x285 | 880x638x310 | 880x798x310 | 880x798x310 | 940x998x330 |
Weight | Kg | 32.0 | 33.0 | 44.5 | 57.5 | 57.5 | 76.5 | |
Refrigerant | ||||||||
Refrigerant | Type | |||||||
Pre-filling | Kg | 0.98 | 1.18 | 1.55 | 2.00 | 2.0 | 2.70 | |
Max length with pre-filling | Mr | 30.0 | 30.0 | 30.0 | 30.0 | 40.0 | 40.0 | |
Co2 pre-filling, equivalent | tCO2e | 0.66 | 0.80 | 1.05 | 1.35 | 1.35 | 1.82 | |
Refrigerant refill | g/m | - | - | 10 | 10 | 20 | 10 | |
Connecting the piping | Liquid | Thumb | 1/4x2 | 1/4x2 | 1/4x2 | 14x3 | 144 | |
Gas | Thumb | 3/8x2 | 3/8x2 | 3/8x2-1/2 | 3/8-1/2x2 | 3/8x2-1/2x2 | 3/8x2-1/2x3 | |
Length of driving | Total length of piping | Mr | 30 | 30 | 50 | 50 | 70 | 75 |
Min/Max - per unit int. | Mr | 3/25 | 3/25 | 3/25 | 3/25 | 3/25 | 3/25 | |
Length of driving | Max height (UI-UI) | Mr | 7.5 | 7.5 | 7.5 | 7.5 | 7.5 | 7.5 |
Max height (EU-UI) | Mr | 15 | 15 | 15 | 15 | 15 | 15 |